In Australia the Input voltage is defined as 230Vac -6%/+10%. This effectively means that the voltage range of these products are 216Vac - 253Vac or 240V +6%
Maximum Wattage
6 W
Standby Power
2.5 W
Standby power for non-maintained/switched maintained emergency devices is measured when the light is off and the charger is in standby mode. For maintained emergency devices, standby power is measured when the light is on and the charger is in standby mode. Typically, charging occurs for the first 16 hours after the device is powered or after a battery discharge.
Driver
Dimmable
No
Driver Included
Yes
Driver Type
Wireless (IEC62386-104) with DT1
Wiring Type
Re-wireable terminal block (5 pin)
Emergency (EM suffix)
Replacement Battery Code
01303
Emergency Classification
C0:C12.5, C90:C20
Emergency Control
IEC62386-104 (Wireless DT1)
IEC62386-104 ~ Supports wireless test and monitoring over IEC62386-104 using IEC62386-202.
Decal Size
300 x 150 mm
Emergency Duration
90 mins
Emergency Mode
Maintained
Viewing Distance
24 m
Compliance
Product Design Life
8 years
The product design life relates to the total product life which includes LEDs, drivers and the enclosure. This is different to the LED lifetime which only refers to the economical lifetime of the LEDs at which time the lumen output has dropped below the L Value. The product design life is calculated at the maximum ambient or working temperature of the product and takes into account the Daily Use.